Installation requirements for diesel generating sets
- Jan 26, 2018 -

Diesel generator sets should be left around 1 meters space, the water tank end according to the size of the tank core retained ventilation window. This requirement is the minimum size of the machine room, the user can increase according to the need.

The foundation of the diesel generator set should be built on the hard land surface, tamping, make the 200mm thick concrete ground, the ground should be flat.

Users in the construction of the computer room, should be in the top of the roof of the unit to be embedded lifting steel beams for future maintenance.

The room should be well ventilated and the ground should be flat and non-slip.

Unit exhaust pipe diameter should not be smaller than the diesel exhaust port diameter, bending pipe should not be more than 3, bending angle should be greater than 90 degrees, the exhaust pipe should be supported or hoisting bracket to ensure that the unit muffler, supercharger and other forces.

The room should be equipped with fire extinguishers and other tools.