Home > Product > Generator Sets > Diesel Generator Sets

125 KVA Diesel Generator Set

125kva diesel generator set Standard Configuratio n ● Engine( Cummins 6BT5.9-G2 ) ● Radiator 50℃ max, fans are driven by belt, with safety guard ● 24V charge alternator ● Alternator: single bearing alternator IP23, insulation class H/H ● Absorber ● Dry type air filter, fuel filter, oil filter ●...

Send InquiryChat Now
Product Details

125kva diesel generator set

Code

SCDG-100

Rated Power(50HZ)

100KW/125KVA

Standby Power(50HZ)

110KW/138KVA


Model

Gensets Power (Prime/Standby)

Engine Brand & Model

Cyl.

Dis.

Oil

Fuel Consumption

Size

Weight

(KW/KVA)

(1500rpm)

(L)

(L)

(g/kw.h)/( L/ h)

(mm)

(kg)

SCDG-100

100/125

110/138

Cummins

6BTA5.9-G2

6

5.9

16.4

207/24

2200*860*1460

1350


QQ截图20171113102011.pngStandard Configuration

● Engine(Cummins 6BT5.9-G2 )

● Radiator 50℃ max, fans are driven by belt, with safety guard

● 24V charge alternator

● Alternator: single bearing alternator IP23, insulation class H/H

● Absorber

● Dry type air filter, fuel filter, oil filter

● Main line circuit breaker

● Standard control panel

● Two12V batteries, rack and cable

● Ripple flex exhaust pipe, exhaust siphon, flange, muffler

● User manual


QQ截图20171113102011.pngEngine Data

1. Basic parameter

Engine Model

Cummins 6BT5.9-G2

Engine Features

In-line, 6 Cylinders, Four-stroke

Rated Power

100KW /1500rpm

Standby Power

110KW /1500rpm

Displacement

5.9L

Bore*Stroke

102*120 mm

Compression Ratio

17.3:1

Mode of Speed Regulation

Electronic

Net Weight

425 KG

Over Dimension

1110*750*988 mm

2. Exhaust Air System

Exhaust air capacity

16.8 m³/min

Exhaust air temperature

565 ℃

Max. exhaust back pressure

10 kPa


QQ截图20171113102011.pngAlternator Data

Number of Phase

3

Connecting Type

3 Phase and 4 Wires, "Y" type connecting

Number of Bearing

1

Power Factor

0.8

Protection Grade

IP23

Altitude

≤1000m

Exciter Type

Brushless, self-exciting

Insulation Class, 

Temperature Rise

H/H

Telephone Influence Factor (TIF)

<50

THF

<2%

Alternator Capacity

125KVA

Alternator Efficiencies

90.3%


QQ截图20171113102011.pngGenerator Data

Voltage Regulation

≥±5%

Voltage Regulation, Stead State

≤±1%

Sudden Voltage Warp (100% Sudden Reduce)

≤+25%

Sudden Voltage Warp (Sudden Increase)

≤-20%

Voltage Stable Time (100% Sudden Reduce)

≤6S

Voltage instability

≤1S

Frequency drop

≤5%

Frequency Waving

≤1.5%

Sudden Frequency Warp (100% Sudden Reduce)

≤+12%

Sudden Frequency Warp (Sudden Increase)

≤-10%

Frequency Recovery Time

≤5S


QQ截图20171113102011.pngStandard Features

● Sanchai Standard  Auto Control System

● Base Fuel Tank

● Starting batteries (Maintenance-Free &Watering-Free) with connective

● MCCB

● Oil Drain Valve

● Exhaust System( including until muffler)

● Special tool for Sanchai engine

● One set of fuel filter / oil filter /belt

● Documents


QQ截图20171113102011.pngDimension &Weight

Open Type with Base Fuel Tank

Overall Size

2300×830×1700(mm)

Weight

1330kg

Soundproof Type

Overall Size

2810×1140×1830(mm)

Weight

1850kg


Hot Tags: 125 KVA diesel generator set, manufacturers, suppliers, factory, customized, cheap, buy discount, low price