Home > Product > Generator Sets > Diesel Generator Sets
Cummins 1475 kva Generator Set

Cummins 1475 kva Generator Set

CCEC 1475kva generator set Ø Standard Configuration  Engine(Cummins KTA50-GS8 )  Radiator 400C max, fans are driven by belt, with safety guard  24V charge alternator  Alternator: single bearing alternator IP23, insulation class H/H  Absorber  Dry type air filter, fuel filter, oil filter,...

Send InquiryChat Now
Product Details

CCEC 1475kva generator set

Code

SCDG-1180

Rated Power(50HZ)

1180KW/1475KVA

Standby Power(50HZ)

1320KW/1650KVA


Model

Gensets Power (Prime/Standby)

Engine Brand & Model

Engine Power    (Prime/Standby)

Cyl.

Dis.

Oil

Fuel Consumption

Size

Weight

(KW/KVA)

(1500rpm)

(kw)

(L)

(L)

(g/kw.h)/( L/ h)

(mm)

(kg)

SCDG-1180

1180/1475

1320/1650

Cummins

KTA50-GS8

1287

1429

16

50.3

204

205/281.3

4980*2200*2480

11000


Ø Standard Configuration

 Engine(Cummins KTA50-GS8 )

 Radiator 400C max, fans are driven by belt, with safety guard

 24V charge alternator

 Alternator: single bearing alternator IP23, insulation class H/H

 Absorber

 Dry type air filter, fuel filter, oil filter, coolant filter

 Main line circuit breaker

 Standard control panel

 Two12V batteries, rack and cable

 Ripple flex exhaust pipe, exhaust siphon, flange, muffler

 User manual

Ø Generator Ratings


Voltage


HZ


Phase


P.F

(COS¢)

Standby

Ratings

(KW/KVA)

Prime

Ratings

(KW/KVA)

220/380

50

3

0.8

1180/1475

1320/1650

Prime Power (PRP): Prime power is available for an unlimited number of annual hours in variable load  application, in accordance with GB/T2820-97(eqvISO8528); A 10% overload capability is available for a period of 1 hour within a 12-hour period of operation.

Standby Power Rating (ESP): The standby power rating is applicable for supplying emergency power for the duration of a utility power interruption. No overload, utility parallel  or negotiated outage operation capability is available at this rating.

Ø Engine Data

1. Basic parameter

Engine Model

Cummins KTA50-GS8

Engine Features

V type , 12 Cylinders, Four-stroke

Rated Power

1180KW /1500rpm

Standby Power

1320KW /1500rpm

Displacement

50.3 L

Bore*Stroke

159*159 mm

Compression Ratio

13.9:1

Mode of Speed Regulation

Electronic


Ø Alternator Data

Alternator brand and model

XINGNUO / XN7f

Number of Phase

3

Connecting Type

3 Phase and 4 Wires, “Y” type connecting

Number of Bearing

1

Power Factor

0.8

Protection Grade

IP23

Altitude

≤1000m

Exciter Type

Brushless, self-exciting

Insulation Class,

Temperature Rise

H/H

Telephone Influence Factor (TIF)

<50

THF

<2%

Alternator Capacity

1500KVA

Alternator Efficiencies

94.9%


Ø Generator Data

Voltage Regulation

≥±5%

Voltage Regulation, Stead State

≤±1%

Sudden Voltage Warp (100% Sudden Reduce)

≤+25%

Sudden Voltage Warp (Sudden Increase)

≤-20%

Voltage Stable Time (100% Sudden Reduce)

≤6S

Voltage Stable Time (Sudden Increase)

≤6S

Frequency Regulation, Stead State

≤5%

Frequency Waving

≤0.5%

Sudden Frequency Warp (100% Sudden Reduce)

≤+12%

Sudden Frequency Warp (Sudden Increase)

≤-10%

Frequency Recovery Time (100% Sudden Reduce)

≤5S

Frequency Recovery Time (Sudden Increase)

≤5S


Ø Standard Features

 Sanchai Standard Auto Control System

 Base Fuel Tank

 Starting batteries(Maintenance-Free &Watering-Free) with connective

 MCCB

 Oil Drain Valve

 Exhaust System( including until muffler)

 Special tool for Sanchai engine

 One set of fuel filter / oil filter /belt

 Documents